Communication Protocols
The release firmware provides MQTT/MQTTS and Modbus RTU. MQTT connects to the platform for reports and commands. Modbus RTU acts as a master, polls RS485 slave devices and maps results to local peripheral data.
Configuration
| Protocol | Web Page | API |
|---|---|---|
| MQTT/MQTTS | Communication Protocols -> MQTT | /api/protocol/mqtt/config, /api/mqtt/status |
| Modbus RTU | Communication Protocols -> Modbus RTU | /api/protocol/modbus-rtu/config, /api/modbus/* |
Confirm networking first, then save protocol settings and inspect status and logs. A successful save does not prove that the remote endpoint is reachable.
MQTT/MQTTS
Supported behavior:
- Plain MQTT, commonly port
1883, and TLS MQTTS, commonly port8883. - Client ID, username/password, keep-alive and last-will configuration.
- Reconnect, properties/events/monitoring reports and platform command subscriptions.
- WiFi, W5500 and EC801E-CN network transports when their features and hardware are active.
Setup:
- Confirm
mqttis compiled and enabled. Enablemqttsonly when TLS is required and memory is sufficient. - Enter broker, port, Client ID and credentials.
- Configure publish/subscribe topics, save and connect.
- Confirm
connectedin/api/mqtt/statusbefore testing platform messages.
/api/mqtt/test saves the submitted configuration and reconnects the main client. Automated tests must restore the original configuration afterward.
Modbus RTU
The current release provides Modbus master behavior:
- UART TX/RX and optional DE pin.
- Multiple slave addresses, function codes, register ranges and data-type mapping.
- Scheduled polling, adjacent-register read merging, retries and timeout metrics.
- Coil/register writes and Peripheral Exec integration.
Setup:
- Wire the RS485 transceiver and verify A/B polarity, ground, termination and DE/RE control.
- Select UART, baud, parity and stop bits on the Modbus page.
- Add a slave device with its address and register map.
- Inspect poll success/failure counters before creating rules or MQTT reports.
Modbus slave response mode is disabled in release builds with FASTBEE_MODBUS_SLAVE_ENABLE=0.
Rule Integration
RS485 slave -> poll task -> register mapping -> local sensor cache
|
condition/action
|
GPIO, display or MQTTA rule supports up to three triggers and four actions. See Peripheral Exec.
Troubleshooting
| Symptom | Check First |
|---|---|
| MQTT does not connect | DNS, broker/port, credentials, Client ID, TLS feature and system time |
| MQTT reconnects repeatedly | Network signal, keep-alive, broker logs and device memory |
| Every Modbus request times out | A/B polarity, baud/parity, slave address, DE pin and common ground |
| Some registers are wrong | Function code, register base, byte order, data type and scaling |
| A rule does not run | modbus feature, poll task, target peripheral and rule enabled state |
See API Reference for status fields and errors, and Network Configuration for transports.