Example 54: Modbus Sensor Device Configuration ​

Scenario Overview ​

Connect external sensor devices (such as temperature/humidity transmitters, air quality sensors, soil sensors, etc.) via Modbus RTU protocol to achieve industrial-grade data acquisition and remote monitoring.

Applicable Devices ​

Device TypeTypical ModelMeasured Parameters
Temp/Humidity TransmitterSHT20/SHT30 RS485Temperature, Humidity
Air Quality SensorPM2.5/CO2 RS485PM2.5, CO2 concentration
Soil SensorSoil 3-in-1 RS485Temperature, Humidity, Conductivity
Light SensorBH1750 RS485Illuminance (Lux)

Hardware Wiring ​

RS485 Interface Connection ​

ESP32 PinTTL-to-RS485 ModuleDescription
GPIO 16 (TX)TXDSerial transmit
GPIO 17 (RX)RXDSerial receive
GPIO 4 (optional)DE/REDirection control (half-duplex)
3.3VVCCPower
GNDGNDGround

RS485 bus connection:

ESP32 ──── TTL-to-RS485 ──── A/B Bus ──┬── Sensor 1 (Address 1)
                                        ├── Sensor 2 (Address 2)
                                        └── Sensor 3 (Address 3)

A 120Ω terminating resistor is recommended at the end of the RS485 bus.

Data Reporting Format ​

Each sensor data is reported independently:

json
[
  {"id": "modbus_temp_humi", "value": "temperature:25.3,humidity:60.5"},
  {"id": "modbus_air", "value": "pm25:35,co2:450"},
  {"id": "modbus_soil", "value": "soil_temp:22.1,soil_moisture:45.3,soil_ec:120"}
]

Peripheral Execution Linkage ​

Scenario 1: Temperature Exceeds Limit Triggers Fan (Poll Trigger) ​

Function: Turn on fan relay when temperature exceeds 30°C

Web Interface Configuration Steps ​

Step 1: Ensure Peripherals are Configured

  • Modbus Temp/Humidity: modbus_temp_humi
  • Fan Relay: relay_fan (GPIO output)

Step 2: Create Rule

  1. Click Peripheral Execution in the left menu
  2. Click Add Rule button
  3. Fill in basic configuration:
    • Rule Name: High Temp Fan On
    • Report Data: ✅ Enabled
    • Enable: ✅ Enabled

Step 3: Configure Trigger (Poll Trigger)

  1. Click Add Trigger button

  2. Fill in trigger configuration:

    FieldValueDescription
    Trigger TypeSelect Poll TriggerTimed condition detection
    Target PeripheralSelect modbus_temp_humiModbus Temp/Humidity
    Data FieldtemperatureTemperature field
    Operator>Greater than
    Threshold3030°C
    Poll Interval50005 seconds

Step 4: Configure Action

  1. Click Add Action button

  2. Fill in:

    • Action Type: Select HIGH
    • Target Peripheral: Select relay_fan
  3. Click Save button


Scenario 2: CO2 Exceeds Limit Alarm (Poll Trigger) ​

Function: Trigger buzzer alarm when CO2 concentration exceeds 1000ppm

Configuration Steps:

  1. Create a rule, name: CO2 Exceed Alarm
  2. Trigger configuration:
    • Trigger Type: Select Poll Trigger
    • Target Peripheral: Select modbus_air
    • Data Field: co2
    • Operator: >
    • Threshold: 1000
    • Poll Interval: 10000
  3. Action configuration:
    • Action Type: Select HIGH
    • Target Peripheral: Select buzzer1 (buzzer must be configured in advance)
  4. Click Save

Debugging Tips ​

  1. Address Scan: Use the built-in Modbus scan feature to confirm slave addresses first
  2. Baud Rate Matching: Ensure all devices use the same baud rate (common: 9600/4800)
  3. Register Confirmation: Consult device manual to confirm register start address and data format
  4. Bus Isolation: When debugging, connect devices one by one; connect all only after confirming communication is normal

Notes ​

  1. Bus Length: RS485 bus maximum 1200m, but recommend not exceeding 100m in practice
  2. Device Count: Maximum 32 slaves per bus; add repeater if exceeded
  3. Polling Conflict: Stagger the interval of multiple devices to avoid simultaneous requests
  4. Data Format: Register formats may differ by manufacturer (big-endian/little-endian, integer/float); adjust scale per manual
  5. Power Isolation: In industrial environments, recommend electrical isolation for RS485 interface to avoid ground loop interference