Communication Protocols
The device provides two protocol links: MQTT/MQTTS and Modbus RTU. MQTT handles platform connectivity, property/event reporting, and command delivery; Modbus RTU acts as a master that polls RS485 slaves and maps the results to local peripheral data.
Page Guide
Configuration Entries
| Protocol | Page | API |
|---|---|---|
| MQTT/MQTTS | Communication Protocols → MQTT | /api/protocol/mqtt/config, /api/mqtt/status |
| Modbus RTU | Communication Protocols → Modbus RTU | /api/protocol/modbus-rtu/config, /api/modbus/* |
| Seniverse Weather and Legacy Resource Migration | Device Screen → Seniverse Weather component | /api/screen-panel/weather |
Confirm the network is online first, then save the protocol configuration. After saving, check the status and device logs; do not judge connection success solely by "saved".

MQTT/MQTTS
Supported:
- Plain MQTT (commonly port
1883) and TLS-encrypted MQTTS (commonly port8883). - Custom Client ID, username/password, Keep Alive, and last-will messages.
- Auto-reconnect, event reporting, property/monitoring data reporting, and platform command subscription.
- WiFi, W5500, and EC801E-CN 4G network transports.
Configuration steps:
- Confirm the device network is online and enable the connection on the MQTT page; when using MQTTS, also enable
mqttsin "Feature Configuration". - Fill in the server, port, Client ID, and credentials on the MQTT page.
- Select the required publish/subscribe topics, save, and connect.
- Confirm
connectedin/api/mqtt/statusor the dashboard, then verify platform messages.
/api/mqtt/test saves a restore record first, then temporarily applies the parameters for a connection-only test; business reporting and subscriptions are isolated, and restoration is attempted afterward. If restoration is pending, keep the evidence and verify the status; a successful handshake does not mean the platform received business messages.
Topic Configuration
Topics are determined by the publish/subscribe lists on the page; common types include:
| Type | Purpose |
|---|---|
property | Sensor and peripheral property reporting |
info | Device information/configuration messages |
event | Button, fault, alarm, and device events |
monitor | Status monitoring |
ntp | Time synchronization |
| HTTP upgrade | Implemented remote upgrade control and results, subject to compile and partition capabilities |
Do not hardcode topic prefixes in integration programs; read the actual configuration or use platform-assigned topics.
Modbus RTU
The current firmware provides Modbus master capability by default:
- UART TX/RX and optional DE pin configuration.
- Multiple slave addresses, function codes, register ranges, and data-type mapping.
- Scheduled polling, adjacent-register read merging, failure retries, and timeout statistics.
- Coil/register writes, and integration through Peripheral Execution rules.
Configuration steps:
- Wire the RS485 transceiver; confirm A/B, GND, termination resistors, and DE/RE direction control.
- Select the UART, baud rate, parity, and stop bits on the Modbus page.
- Add slave devices with their addresses and register mappings.
- After saving, check the poll success/failure counters before creating rules or MQTT reports.
The Modbus slave response feature is disabled by default (FASTBEE_MODBUS_SLAVE_ENABLE=0); do not configure this device as a slave following slave-device documentation.
Rule Integration
Modbus reads are handled by the existing scheduler and bus arbitration; currently valid mapped data can be used by independent event rules. Do not treat an output immediately following a collection action as threshold gating.
RS485 slave -> poll task -> register mapping -> local sensor cache
|
rule conditions/actions
|
GPIO, display, or MQTTA rule supports up to 3 triggers and 4 actions; for detailed configuration see Peripheral Execution.
Troubleshooting
| Symptom | Check First |
|---|---|
| MQTT not connected | DNS, server/port, credentials, Client ID, TLS feature, and system time |
| MQTT reconnects frequently | WiFi signal, Keep Alive, broker logs, and device memory |
| All Modbus requests time out | A/B reversed, baud rate/parity, slave address, DE pin, and common ground |
| Individual registers abnormal | Function code, register base, byte order, data type, and scaling factor |
| Rule takes no action | modbus feature, poll task, target peripheral, and rule enabled state |
For interfaces, status fields, and error codes, see the API Reference; for network transports, see Network Configuration.
The current PubSubClient publish actually uses QoS 0; a publish configuration of qos=1 does not provide QoS 1 delivery guarantees. Subscribe and last-will QoS are handled separately. The legacy remote channel is retired: the related old APIs return 410, and rules bound to the retired source are suspended as a whole. See each topic page for detailed boundaries.
FAQ
Does "saved" after saving the protocol configuration mean the connection succeeded?
No. Saving only writes the configuration; the connection counts as successful only after connected is confirmed in /api/mqtt/status or the dashboard, and platform message exchange is verified.
Can I configure this device as a Modbus slave?
No. The Modbus slave response feature is disabled by default (FASTBEE_MODBUS_SLAVE_ENABLE=0); the current firmware provides master capability only. Do not configure this device as a slave following slave-device documentation.
Does a publish configuration of qos=1 provide QoS 1 delivery guarantees?
No. The current PubSubClient publish actually uses QoS 0; subscribe and last-will QoS are handled separately. Do not take the publish configuration as evidence of delivery guarantees.
Can I hardcode topic prefixes in integration programs?
No. Topics are determined by the publish/subscribe lists on the page; integration programs should read the actual configuration or use platform-assigned topics.