Example 45: Modbus Temp/Humidity Sensor ​

Experiment Overview ​

Reads RS485 temperature and humidity transmitter data (e.g., SHT20/SHT30 RS485 type) via Modbus RTU protocol. This is the most common sensor integration method in industrial environments, suitable for greenhouses, server rooms, warehouses, and similar monitoring scenarios.

Hardware Wiring ​

RS485 Communication Wiring ​

ESP32 PinTTL-to-RS485 ModuleDescription
GPIO 16TXDSerial transmit
GPIO 17RXDSerial receive
GPIO 4 (optional)DE/REDirection control
3.3VVCCPower
GNDGNDGround

RS485 Bus to Sensor ​

RS485 ModuleTemp/Humidity TransmitterDescription
A+A+Differential signal positive
B-B-Differential signal negative

A 120Ω termination resistor is recommended at the end of the bus; multiple devices can be connected to the same bus with different slave addresses.

JSON Configuration Example ​

json
{
  "id": "modbus_th",
  "name": "Modbus Temp/Humidity Sensor",
  "type": 1,
  "enabled": false,
  "pins": [16, 17],
  "params": {
    "baudRate": 9600,
    "dataBits": 8,
    "parity": "none",
    "stopBits": 1,
    "dePin": 4,
    "protocol": "modbus_rtu",
    "slaveId": 1,
    "function": 3,
    "startRegister": 0,
    "registerCount": 2,
    "interval": 5000,
    "dataMap": [
      { "register": 0, "name": "temperature", "scale": 0.1, "unit": "°C" },
      { "register": 1, "name": "humidity", "scale": 0.1, "unit": "%" }
    ]
  }
}

Parameter Description ​

ParameterDescription
slaveIdSlave address (factory default is usually 1; can be modified via DIP switch or command)
functionModbus function code; 3 for reading holding registers
startRegisterStarting register address (varies by manufacturer; check manual)
registerCountNumber of registers to read
intervalPolling interval (ms)
dataMapMapping from registers to data fields; scale is the scaling factor

Data Reporting ​

Sensor data is reported via MQTT:

json
[{"id": "modbus_th", "value": "temperature:25.3,humidity:60.5"}]

Peripheral Execution Linkage ​

Scenario 1: High Temperature Alarm (Polling Trigger) ​

Feature: Trigger buzzer alarm when temperature exceeds 35°C

Web UI Configuration Steps ​

Step 1: Ensure Buzzer Peripheral is Configured

  • Peripheral ID: buzzer_gpio
  • Type: GPIO Output

Step 2: Create Rule

  1. Click Peripheral Execution in the left menu
  2. Click New Rule button
  3. Fill in basic configuration:
    • Rule Name: Temp/Humidity Alarm
    • Report Data: ✅ Enabled
    • Enable: ✅ Enabled

Step 3: Configure Trigger (Polling Trigger)

  1. Click Add Trigger button

  2. Fill in trigger configuration:

    FieldValueDescription
    Trigger TypeSelect Polling TriggerPeriodic condition check
    Target PeripheralSelect modbus_thModbus temp/humidity
    Data FieldtemperatureTemperature field
    Operator>Greater than
    Threshold3535°C
    Polling Interval50005 seconds

Step 4: Configure Action

  1. Click Add Action button

  2. Fill in:

    • Action Type: Select HIGH
    • Target Peripheral: Select buzzer_gpio
  3. Click Save button


Scenario 2: OLED Display Linkage (Timer Trigger) ​

Feature: Periodically display temperature and humidity data on OLED

Configuration Steps:

  1. Create rule, name: Display Temp/Humidity
  2. Trigger configuration:
    • Trigger Type: Select Timer Trigger
    • Interval: 5000 (5 seconds)
  3. Action configuration (2 actions required):
    • Action 1: Select Sensor Read, target modbus_th
    • Action 2: Select Display Control, target oled1, template Temp:{modbus_th.temperature}C\nHumi:{modbus_th.humidity}%
  4. Click Save

Notes ​

  1. Address Confirmation: Use the system Modbus scan feature to confirm slave address; factory address may not be 1
  2. Register Format: Temperature register may be signed integer (requires scale=0.1) or float, depending on manufacturer
  3. Baud Rate Matching: Sensor and ESP32 baud rates must match; common values are 4800/9600
  4. Wiring Polarity: A+/B- must not be reversed, otherwise communication will fail
  5. Power Requirements: RS485 sensors typically require 12-24V DC power; independent power supply needed
  6. Bus Length: Longer bus = worse interference resistance; use shielded twisted pair for distances over 50m