IEC104 and TCP Remote Signalling Station Access
This article reorganizes an existing operation manual into an online operation reference. Operations marked as expected or not executed in the original must still be verified against the actual environment.
Complete IEC104 ten-address remote signalling, two native single commands, independent states and history queries, plus a normal stop and republish recovery.
Before you begin: You have product, device, model, publish, control, and history permissions; the local application, single-node FMQ, and FMQX Web are available, and this device's connection parameters have been obtained
Learn This First
This article uses FMQX Web as the IEC104 controlled station, listening on TCP 15040; FMQ connects as the master station, and the platform manages products, devices, point tables, publish, and history.
Common address 1 identifies the controlled station; information object addresses 1001 to 1010 identify the ten remote signalling points respectively. true displays as Closed and false as Open.
This round's ten samples are one per address, odd true and even false; both single-point controls target 1001 — first false, then true after recovery.
Replace These Parameters Before Copying Templates
The code in this article uses generic template names; the screenshots retain actual historical resources. Complete the following checks before saving as a UTF-8 file or sending messages.
- The host, port, and listening direction in the connection file must be changed to the actual addresses of the current environment; 127.0.0.1 means the local machine running FMQX. When MQTT is involved, also verify the product ID, username, subscription topics, and responseRoute; passwords are only entered securely on the connection page.
- Group, session, and subscription ids are internal references of the import file; if renaming is needed, the groupId must match the corresponding group id. Verify before importing, and do not repeatedly create connections with the same name on a retained session.
- The code blocks are customer templates rewritten from existing password-free assets or original code; this version of the template has not yet been proven to import successfully. Historical screenshots, send times, and business pass scope are still subject to the records of each step; do not treat template names as the actual resource names in the old evidence.
1. Creating the Product and Configuring the Protocol
This article reuses the first modeling, binding, mapping, and FMQX import records from 2026-10-13; this round reuses product 887, device 1244, and the existing session, without recreating, saving the model, or importing again.
The odd-false, even-true values in the first JSON screenshot were only used for modeling; this round's actual samples start from the later reporting section.
1. Creating Ten Boolean Properties from a Sample
Location: Device Access Wizard → JSON Sample Steps: Enter the ten remote signalling field sample and click Parse Preview; this step is only for modeling.

Use ten boolean fields to build the thing model; the sample is only used to identify fields and types — actual remote signalling is reported over IEC104.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| First Modeling Sample | The historical JSON generates ten boolean models; the sample is odd false and even true and is not used as this round's report values. Required · Fill in: Odd fields false; even fields true |
2. Verifying the Fields and Boolean Type
Location: Device Access Wizard → Collection Point Table Steps: Verify the identifiers and boolean type of the ten fields, corresponding in address order.

Verify the ten fields and their boolean type item by item, building the mapping in the address order of the formal point table.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| First Modeling Sample | The historical JSON generates ten boolean models; the sample is odd false and even true and is not used as this round's report values. Required · Fill in: Fill according to the implementation plan · Example: Ten boolean fields |
| Information Object Address | Ten independent remote signalling addresses; 1001 is this article's writable point. Required · Fill in: Fill according to the implementation plan · Example: 1001–1010; control 1001 |
| Remote Signalling Type | Single-point remote signalling maps to BOOLEAN; true is Closed, false is Open. Required · Fill in: Fill according to the implementation plan · Example: M_SP_NA_1 / BOOLEAN |
| Modeling Sample | JSON is only used to generate the ten boolean models; the final selection is native IEC104. Required · Fill in: 10 boolean fields |
| Information Object Address (ioa) | The independent address of each remote signalling point in the point table; it is not the common address. Required · Fill in: 1001–1010 |
| Remote Signalling Type (asduType) | This article uses single-point remote signalling, with values true/false. Required · Fill in: M_SP_NA_1 / BOOLEAN |
3. Filling in This Article's Device Identity
Location: Device Access Wizard → Device Information Steps: Fill in the independent device number and name for later binding.

Fill in a unique device number and name for this device.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Device Identity | The independent device number stays identical to the platform-bound clientId. Required · Fill in: This article's controlled station |
4. Switching to the Final Native Protocol
Location: Product Details → Basic Information Steps: Select TCP and IEC 60870-5-104, then save the changes.

Select TCP as the access channel and IEC 60870-5-104 as the data format.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Access Protocol and Data Format | FMQ connects to the controlled station as the master station, using native IEC104. Required · Fill in: TCP / IEC 60870-5-104 |
5. Enabling History and Allowing Remote Signalling 1 Control
Location: Product → Function Definition → Modify Thing Model Steps: Turn off read-only data for Remote Signalling 1 and enable history storage; keep the other nine items read-only with history enabled.

Enable history storage; Remote Signalling 1 allows control, and the other nine items remain read-only.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Property Permission and History | All ten items have history enabled; 1001 allows control, and the other nine items are read-only. Required · Fill in: Fill according to the implementation plan · Example: Ten boolean properties; 1001 writable |
| Property Permission and History | Remote Signalling 1 allows control; the rest are read-only, and all ten items have history storage enabled. Required · Fill in: Boolean; 1001 writable; history on |
6. Binding the Device and the Controlled Station Address
Location: Product → Device Protocol Configuration → Device Binding Steps: Select this device, fill in the clientId, common address, IP, and port, enable, and save the draft.

Fill in the actual controlled station's IP, port, and common address; FMQ actively establishes the connection as the master station.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Device Binding | deviceId 1244, clientId is this device's number; enable the binding. Required · Fill in: This device / common address 1 |
| Common Address | Identifies the station; keep the platform binding and native messages consistent. Required · Fill in: Fill according to the implementation plan · Example: 1 |
| Controlled Station IP | The platform binding fills in the controlled station's reachable listening IP; the local demo uses the loopback address. Required · Fill in: 127.0.0.1 |
| Controlled Station Port | The platform binding stays consistent with the imported controlled station's listening port. Required · Fill in: 15040 |
| Common Address (commonAddress) | The station address provided by the formal point table; binding, remote signalling, general interrogation, and remote control must all be consistent. Required · Fill in: 1 |
7. Saving the Address and Remote Signalling Mapping
Location: Device Protocol Configuration → Point Mapping Steps: Configure 1001 to 1010 according to the point table, single-point remote signalling and BOOLEAN, scale 1, offset 0; only 1001 is writable.

The ten remote signalling addresses are 1001 to 1010, corresponding to thing model fields item by item.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Information Object Address | Ten independent remote signalling addresses; 1001 is this article's writable point. Required · Fill in: Fill according to the implementation plan · Example: 1001–1010; control 1001 |
| Remote Signalling Type | Single-point remote signalling maps to BOOLEAN; true is Closed, false is Open. Required · Fill in: Fill according to the implementation plan · Example: M_SP_NA_1 / BOOLEAN |
| Scale and Offset | The boolean demo keeps scale 1 and offset 0, with the unit left blank. Required · Fill in: 1 / 0; unit left blank |
| Property Permission and History | All ten items have history enabled; 1001 allows control, and the other nine items are read-only. Required · Fill in: Fill according to the implementation plan · Example: Ten boolean properties; 1001 writable |
| Information Object Address (ioa) | The independent address of each remote signalling point in the point table; it is not the common address. Required · Fill in: 1001–1010 |
| Remote Signalling Type (asduType) | This article uses single-point remote signalling, with values true/false. Required · Fill in: M_SP_NA_1 / BOOLEAN |
| Property Permission and History | Remote Signalling 1 allows control; the rest are read-only, and all ten items have history storage enabled. Required · Fill in: Boolean; 1001 writable; history on |
8. Setting the Normal General Interrogation Cycle
Location: Device Protocol Configuration → Collection Group Steps: Fill in common address 1, enable general interrogation, set the interval to 60000 milliseconds, and enable.

Configure periodic general interrogation; 60000 milliseconds means requesting the current point values once per minute.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Common Address | Identifies the station; keep the platform binding and native messages consistent. Required · Fill in: Fill according to the implementation plan · Example: 1 |
| Historical Collection Group Configuration | The first configuration enabled general interrogation with a 60000-millisecond interval; this only describes the saved items and is not proof of a successful manual general interrogation in this round. Required · Fill in: Fill according to the implementation plan · Example: interrogationEnabled on; 60000 milliseconds |
| Common Address (commonAddress) | The station address provided by the formal point table; binding, remote signalling, general interrogation, and remote control must all be consistent. Required · Fill in: 1 |
| General Interrogation Group | Enables general interrogation, normally asking for the whole-station state every 60 seconds. Required · Fill in: interrogationEnabled on; 60000 ms |
9. Configuring the Single-Point Remote Control Template
Location: Device Protocol Configuration → Command Templates Steps: Common address 1, IOA 1001, type C_SC_NA_1, mapped to Remote Signalling 1; turn off select-before-execute and save the draft.

Single remote control uses common address 1 and information object address 1001, consistent with the writable property Remote Signalling 1.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Single-Point Remote Control Template | Common address 1, information object address 1001, select-before-execute off, using direct execution. Required · Fill in: Fill according to the implementation plan · Example: C_SC_NA_1; selectBeforeExecute off |
| Information Object Address | Ten independent remote signalling addresses; 1001 is this article's writable point. Required · Fill in: Fill according to the implementation plan · Example: 1001–1010; control 1001 |
| Common Address | Identifies the station; keep the platform binding and native messages consistent. Required · Fill in: Fill according to the implementation plan · Example: 1 |
| Remote Control Template | Address 1001 maps to Remote Signalling 1, using single-command direct execution. Required · Fill in: C_SC_NA_1; selectBeforeExecute off |
| Information Object Address (ioa) | The independent address of this article's writable Remote Signalling 1. Required · Fill in: 1001 |
| Common Address (commonAddress) | The station address provided by the formal point table; binding, remote signalling, general interrogation, and remote control must all be consistent. Required · Fill in: 1 |
**Complete connection and point JSON template (password-free)**json
{
"schemaVersion": 3,
"groups": [
{
"id": "tutorial_IEC104_01",
"name": "Remote Signalling Tutorial",
"sortOrder": 80,
"isSystem": false
}
],
"sessions": [
{
"id": "import_IEC104_01",
"name": "Controlled Station",
"groupId": "tutorial_IEC104_01",
"protocol": "IEC104",
"transport": "TCP",
"host": "127.0.0.1",
"port": 15040,
"autoReconnect": false,
"iec104CommonAddress": 1,
"iec104Points": [
{
"informationObjectAddress": 1001,
"type": "M_SP_NA_1",
"value": false,
"writable": true
},
{
"informationObjectAddress": 1002,
"type": "M_SP_NA_1",
"value": true,
"writable": false
},
{
"informationObjectAddress": 1003,
"type": "M_SP_NA_1",
"value": false,
"writable": false
},
{
"informationObjectAddress": 1004,
"type": "M_SP_NA_1",
"value": true,
"writable": false
},
{
"informationObjectAddress": 1005,
"type": "M_SP_NA_1",
"value": false,
"writable": false
},
{
"informationObjectAddress": 1006,
"type": "M_SP_NA_1",
"value": true,
"writable": false
},
{
"informationObjectAddress": 1007,
"type": "M_SP_NA_1",
"value": false,
"writable": false
},
{
"informationObjectAddress": 1008,
"type": "M_SP_NA_1",
"value": true,
"writable": false
},
{
"informationObjectAddress": 1009,
"type": "M_SP_NA_1",
"value": false,
"writable": false
},
{
"informationObjectAddress": 1010,
"type": "M_SP_NA_1",
"value": true,
"writable": false
}
]
}
]
}After verifying against the replacement checklist, save it as 连接配置.json and select Import Configuration in FMQX Web; this rewritten text does not mean the template has actually been imported. Replaceable customer template names are used here; verify against this section's replacement checklist before importing or sending.
10. Importing the FMQX Controlled Station Configuration
Location: FMQX Web → Configuration File Steps: After verifying this section's complete JSON against the replacement checklist, save it as the UTF-8 file 连接配置.json, then select Import Configuration under More Actions in FMQX Web. The original step screenshot retains the original batch operation.

Import the demo controlled station configuration and point table in FMQX Web.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Import Configuration | Imports the controlled station's IP, port, common address, and ten-point table from a configuration file. Required · Fill in: 连接配置.json |
Historical Optional Configuration: Station-Wide General Interrogation Whitelist
The historical general interrogation whitelist configuration is kept to explain address 0. This round did not re-save or execute a manual general interrogation, and the old general interrogation operation, history, or success conclusions are not carried over.
11. Historical Optional Configuration: Adding a Station-Wide General Interrogation Whitelist
Location: IEC104 Workbench → Command Whitelist → Add Steps: Configure the general interrogation whitelist: common address 1, information object address 0, C_IC_NA_1, associated with Remote Signalling 1; turn off select-before-execute and enable. This article's downlink demo uses single remote control.

The general interrogation template uses common address 1, information object address 0, and C_IC_NA_1; this article's control demo uses the single remote control template.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Historical Optional Station-Wide General Interrogation | Only the first whitelist configuration is kept for reference; this round did not re-save or execute a manual general interrogation. Required · Fill in: Common address 1; address 0; C_IC_NA_1 |
2. Verifying Names, Publishing, and Confirming the Connection
The connection editor only provides the name, group, and save method. The native listening parameters come from the imported configuration; verify them together with the platform binding and the current connection summary.
12. Read-Only Verification of the Connection Name and Group
Location: FMQX Web → This Article's Session → Connection Parameters Steps: Verify the connection name, owning group, and save method, then cancel editing.

This window is for the name, group, and save method; the controlled station address and point table come from the imported configuration.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Connection Name | Used to complete "Read-Only Verification of the Connection Name and Group". Required · Fill in: FastBee_受控站 |
| Owning Group | Used to complete "Read-Only Verification of the Connection Name and Group". Required · Fill in: FastBee_遥信教程 |
13. Publishing This Article's Product Configuration
Location: Product Details → Basic Information Steps: First start this article's controlled station listener, then verify this article's product and click OK in the publish confirmation box.

FMQ actively connects to 127.0.0.1:15040 as the master station; after publishing, continue to check node application and STARTDT.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Controlled Station IP | The platform binding fills in the controlled station's reachable listening IP; the local demo uses the loopback address. Required · Fill in: Fill according to the implementation plan · Example: 127.0.0.1 |
| Controlled Station Port | The platform binding stays consistent with the imported controlled station's listening port. Required · Fill in: Fill according to the implementation plan · Example: 15040 |
| Common Address | Identifies the station; keep the platform binding and native messages consistent. Required · Fill in: Fill according to the implementation plan · Example: 1 |
14. Confirming the Runtime Configuration Has Been Applied
Location: Product Details → Sync Details Steps: Open the sync details and verify the target node's APPLIED status and effective time.

Verify the target node shows APPLIED, then check the controlled station connection and actual send/receive.
15. Confirming the Controlled Station Is Connected and STARTDT Is Complete
Location: FMQX Web → Connection Configuration Steps: Verify the role, station address, listening endpoint, point count, and connection status.

Controlled station Server, common address 1, ten points, 127.0.0.1:15040; connected / STARTDT confirmed, 1 active connection.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Common Address | Identifies the station; keep the platform binding and native messages consistent. Required · Fill in: Fill according to the implementation plan · Example: 1 |
| Controlled Station IP | The platform binding fills in the controlled station's reachable listening IP; the local demo uses the loopback address. Required · Fill in: Fill according to the implementation plan · Example: 127.0.0.1 |
| Controlled Station Port | The platform binding stays consistent with the imported controlled station's listening port. Required · Fill in: Fill according to the implementation plan · Example: 15040 |
3. Reporting Ten Different Addresses in Turn
16. Saving and Reporting the First Remote Signalling Point
Location: FMQX Web → Communication → Remote Signalling Point Steps: Set address 1001 to true, save the point, then click Send Telemetry once.

The first sample is 1001=true; saving the demo point value and sending telemetry are done separately.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Set Demo Point Values | Save each of the ten-sample addresses once: odd true, even false; the recovery 1002=true and the second baseline 1001=false are saved separately by the operator. Required · Fill in: Fill according to the implementation plan · Example: 1001–1010 once each |
| Information Object Address | Ten independent remote signalling addresses; 1001 is this article's writable point. Required · Fill in: 1001 |
| Remote Signalling Type | Single-point remote signalling maps to BOOLEAN; true is Closed, false is Open. Required · Fill in: Fill according to the implementation plan · Example: M_SP_NA_1 / BOOLEAN |
| Boolean Value | Used to complete "Saving and Reporting the First Remote Signalling Point". Required · Fill in: true / Closed |
17. Verifying the First Independent Remote Signalling Raw Frame
Location: FMQX Web → Communication Records Steps: Open the 02:05:18.803 send record and verify the raw frame and address.

type1 is single-point remote signalling, cause3 is spontaneous reporting; common address 1, 1001=true, consistent with the first sample.
18. Reporting Ten Different Remote Signalling Points in Address Order
Location: FMQX Web → Communication → Remote Signalling Point Steps: After completing the save, send, and native-frame verification for address 1001 in the previous two steps, continue saving and sending once for each of 1002 to 1010; odd true, even false, waiting for the platform to update each time.

The ten samples correspond to ten different addresses; the tenth address is 1010=false. Wait for the platform to update before operating the next point each time.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Set Demo Point Values | Save each of the ten-sample addresses once: odd true, even false; the recovery 1002=true and the second baseline 1001=false are saved separately by the operator. Required · Fill in: Fill according to the implementation plan · Example: 1001–1010 once each |
| Information Object Address | Ten independent remote signalling addresses; 1001 is this article's writable point. Required · Fill in: Fill according to the implementation plan · Example: 1001–1010; control 1001 |
| Ten Addresses | Used to complete "Reporting Ten Different Remote Signalling Points in Address Order". Required · Fill in: 1001, 1002, 1003, 1004, 1005, 1006, 1007, 1008, 1009, 1010 |
| This Round's Values | Used to complete "Reporting Ten Different Remote Signalling Points in Address Order". Required · Fill in: true, false, true, false, true, false, true, false, true, false |
4. First Platform Remote Control and Independent State
The activation request, activation confirmation, and activation termination correspond to cause6, 7, and 10 respectively; after termination, only select the address and send telemetry — avoid manually saving the value and overwriting the control result.
19. Changing Remote Signalling 1 to Open from the Platform
Location: Device Details → Running Status → Remote Signalling 1 Steps: Verify the current state is Closed, control Remote Signalling 1 to false, send once, then check on the device side.
This image shows true before writing; this target false and the execution result are proven by the subsequent independent native records.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| First Remote Signalling 1 Control | This round controls from true to false; the screenshot shows true before writing. Required · Fill in: Fill according to the implementation plan · Example: 1001: Closed → Open |
| Control Address | Used to complete "Changing Remote Signalling 1 to Open from the Platform". Required · Fill in: 1001 |
| Target Value | Used to complete "Changing Remote Signalling 1 to Open from the Platform". Required · Fill in: false / Open |
20. Confirming the First Remote Control Request Was Received
Location: FMQX Web → Communication Records Steps: View the 02:05:42.740 received frame.

Received a C_SC_NA_1 single command, cause6 is the activation request, common address 1, 1001=false.
21. Confirming the First Remote Control Was Accepted
Location: FMQX Web → Communication Records Steps: View the subsequent 02:05:42.741 sent frame.

The same single command returns cause7 activation confirmation, 1001=false; continue verifying the termination confirmation.
22. Confirming the Native End of the First Remote Control
Location: FMQX Web → Communication Records Steps: View the 02:05:42.742 sent frame.

The device sends the activation termination confirmation, Remote Signalling 1=false; continue verifying the actual state with an independent spontaneous report.
23. Independently Reporting the State After the First Control Without Saving the Point Value
Location: FMQX Web → Remote Signalling Point and Communication Records Steps: Only select address 1001 and send telemetry, keeping the point value unsaved, then verify the new 02:05:44.938 sent frame.

The independent type1/cause3 report is 1001=false and is associated with actual history; this report did not manually save the point value.
5. Republish Recovery After a Normal Stop
This round recovers in the order of normal stop, unpublish, starting the controlled station, and republishing, without injecting network failures. The recovery 1002=true is a new demo value set by the operator.
24. Normally Stopping the Controlled Station Connection
Location: FMQX Web → This Article's Session Steps: After completing the first control, disconnect normally and verify the left side shows Disconnected.

The controlled station has stopped listening, and the connection status shows Disconnected.
25. Unpublishing to Pause This Article's Collection
Location: Product Details → Unpublish Steps: Read the notice that republishing may reset device data, then click OK.

Pause this article's runtime configuration, keeping the product, device, thing model, session, and the history already formed.
26. Confirming the Paused Configuration Has Been Applied
Location: Product Details → Sync Details Steps: Verify the unpublished state and the node application result.

Verify the unpublish has been applied. To recover, start the controlled station first, then republish the product.
27. Republishing After Starting the Controlled Station
Location: FMQX Web → This Article's Session; Product Details → Publish Steps: First start the same controlled station listener, then republish the original product and wait for application; verify the left side shows Connected.

The controlled station is started, the republish has been applied, and the connection is restored; continue sending new remote signalling for verification.
28. Setting and Reporting a New Point Value After Recovery
Location: FMQX Web → Remote Signalling Point and Communication Records Steps: Save 1002 as true, then send, and verify the 02:06:01.571 independent remote signalling frame.

After recovery, report 1002=true and check that the platform receives the new point value.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Set Demo Point Values | Save each of the ten-sample addresses once: odd true, even false; the recovery 1002=true and the second baseline 1001=false are saved separately by the operator. Required · Fill in: Fill according to the implementation plan · Example: 1001–1010 once each |
| Recovery Report | Used to complete "Setting and Reporting a New Point Value After Recovery". Required · Fill in: 1002=true |
6. Executing a New Opposite-Direction Control After Recovery
1001=false is the second pre-write baseline set and sent by the operator; afterwards, the platform controls true, followed by an independent report without saving the point value — verify them separately.
29. Setting the Baseline, Then Changing Remote Signalling 1 to Closed from the Platform
Location: FMQX Web → Remote Signalling Point; Device Details → Running Status Steps: First save 1001 as false and send it at 02:06:03.060 as the manual baseline; verify the platform shows Open, then control it to true from the platform.

This image shows false before the second write; the manual baseline and the remote control execution are verified separately, and the subsequent new native records prove the target true.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Set Demo Point Values | Save each of the ten-sample addresses once: odd true, even false; the recovery 1002=true and the second baseline 1001=false are saved separately by the operator. Required · Fill in: Fill according to the implementation plan · Example: 1001–1010 once each |
| New Control After Recovery | The operator first saves and sends the 1001=false baseline, then the platform controls true. Required · Fill in: Fill according to the implementation plan · Example: 1001: Open → Closed |
| Manual Recovery Baseline | Used to complete "Setting the Baseline, Then Changing Remote Signalling 1 to Closed from the Platform". Required · Fill in: 1001=false |
| Second Platform Target | Used to complete "Setting the Baseline, Then Changing Remote Signalling 1 to Closed from the Platform". Required · Fill in: 1001=true |
30. Confirming the New Remote Control Was Received After Recovery
Location: FMQX Web → Communication Records Steps: View the newly received frame at 02:06:08.622.

Received a new C_SC_NA_1/cause6, common address 1, 1001=true; distinguish it from the first false command.
31. Confirming the Second Remote Control Was Accepted
Location: FMQX Web → Communication Records Steps: View the newly sent activation confirmation at 02:06:08.623.

Returns C_SC_NA_1/cause7, 1001=true.
32. Confirming the Native End of the Second Remote Control
Location: FMQX Web → Communication Records Steps: View the activation termination frame at the same moment right after.

The device sends the activation termination confirmation, Remote Signalling 1=true; continue verifying the independent spontaneous report.
33. Independently Reporting the State After the Second Control Without Saving the Point Value
Location: FMQX Web → Remote Signalling Point and Communication Records Steps: Only select address 1001 and send telemetry without saving the point value, then verify the new 02:06:10.945 sent frame.

The independent type1/cause3 report is 1001=true and forms actual history; the earlier manual false baseline cannot replace this proof.
7. Stopping Operation and Verifying the Retained State
The complete ten-point image was captured after the final stop and only illustrates the retained current values; it cannot replace the ten-sample baseline or the manual general interrogation proof.
34. Ending Send/Receive and Preserving the Session
Location: FMQX Web → This Article's Session Steps: Disconnect normally, and stop scheduled sending and auto reply.

Stop the controlled station listener and turn off auto sending, keeping the session and the point table.
35. Final Unpublish and Confirmation of Application
Location: Product Details → Unpublish and Sync Details Steps: Finally unpublish this article via the confirmation entry above, wait for node application, then verify the sync details.

The unpublish has been applied; the product, device, thing model, session, and history records are preserved.
36. Verifying the Ten-Point Current Values Retained After Stopping
Location: Device Details → Running Status → Real-time Metrics Steps: After stopping send/receive, read the ten remote signalling current values item by item.

All ten points are fully visible: 1001 and 1002 Closed; 1003, 1005, 1007, 1009 Closed, and 1004, 1006, 1008, 1010 Open. This image is the retained state after the end.
8. Filtering, Refreshing, and Verifying History Record by Record
The ten-sample query selects the ten remote signalling points, and each table row has a value only in the column of that record's address. The second window selects Remote Signalling 1, and the six records include two controls, two independent reports, one recovery publish state, and one manual baseline.
37. Filling in the Complete Time Range for the Ten Independent Remote Signalling Samples
Location: Data Center → Historical Data Steps: Fill in this query's complete start and end date-times.

Fill in the complete start and end dates and times, covering the ten reports.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Start Time | Used to complete "Filling in the Complete Time Range for the Ten Independent Remote Signalling Samples". Required · Fill in: 2026-10-16 02:05:17 |
| End Time | Used to complete "Filling in the Complete Time Range for the Ten Independent Remote Signalling Samples". Required · Fill in: 2026-10-16 02:05:31 |
38. Filtering This Article's Device and the Ten Remote Signalling Points
Location: Data Center → Historical Data Steps: Select this controlled station and Remote Signalling 1 to 10, verify the time conditions, then click Query.

The device, fields, and previous complete time range stay consistent.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Fields | Used to complete "Filtering This Article's Device and the Ten Remote Signalling Points". Required · Fill in: Remote Signalling 1–10 |
39. Refreshing the Ten Independent Remote Signalling Sample History
Location: Data Center → Historical Data Steps: Keep the same device, fields, and time conditions, and click the refresh button at the top right of the result area.

After refresh, there are 10 time records in total, each corresponding to one address.
40. Verifying the Ten Independent Remote Signalling Sample History Record by Record
Location: Data Center → Historical Data → Query Results Steps: Verify 1001 to 1010 row by row, by time and field; each row has a value only for that record's address, and the other fields are blank.

02:05:18, 21, 22, 23, 24, 25, 26, 27, 28, 29 correspond to 1001 to 1010 in order, odd true and even false; blank means the record does not have that field, not false.
41. Filling in the Complete Time Range for the Remote Signalling 1 Control and Recovery
Location: Data Center → Historical Data Steps: Fill in this query's complete start and end date-times.

Fill in the complete time range covering the two controls, the recovery, and the independent reports.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Start Time | Used to complete "Filling in the Complete Time Range for the Remote Signalling 1 Control and Recovery". Required · Fill in: 2026-10-16 02:05:41 |
| End Time | Used to complete "Filling in the Complete Time Range for the Remote Signalling 1 Control and Recovery". Required · Fill in: 2026-10-16 02:06:13 |
42. Filtering This Article's Device and Remote Signalling 1
Location: Data Center → Historical Data Steps: Select this controlled station and Remote Signalling 1, verify the time conditions, then click Query.

The device, fields, and previous complete time range stay consistent.
Screenshot Highlights
| Field / Control | Description |
|---|---|
| Fields | Used to complete "Filtering This Article's Device and Remote Signalling 1". Required · Fill in: Remote Signalling 1 |
43. Refreshing the Remote Signalling 1 Control and Recovery History
Location: Data Center → Historical Data Steps: Keep the same device, fields, and time conditions, and click the refresh button at the top right of the result area.

After refresh, there are 6 Remote Signalling 1 time records in total.
44. Verifying the Remote Signalling 1 Control and Recovery History Record by Record
Location: Data Center → Historical Data → Query Results Steps: Verify row by row the two controls, the post-control independent reports, the recovery publish state, and the manual baseline.

02:05:42=false (first control state); 02:05:44=false (independent report); 02:05:58=false (recovery publish state); 02:06:03=false (manual baseline); 02:06:08=true (second control state); 02:06:10=true (independent report).
Where Parameters Come From and How to Fill Them
First Device Access Configuration
| Field / Control | How to Fill |
|---|---|
| First Modeling Sample | The historical JSON generates ten boolean models; the sample is odd false and even true and is not used as this round's report values. Required · Fill in: Ten boolean fields |
| Device Identity | The independent device number stays identical to the platform-bound clientId. Required · Fill in: FastBee_IEC104_Tutorial_01 |
Platform Protocol Configuration and Publish
| Field / Control | How to Fill |
|---|---|
| Access Protocol and Data Format | FMQ connects to the controlled station as the master station, using native IEC104. Required · Fill in: TCP / IEC 60870-5-104Publish after changes.TCP / IEC 60870-5-104: Native IEC104 connects to the controlled station over TCP; use this article's native station address and point table. |
| Controlled Station IP | The platform binding fills in the controlled station's reachable listening IP; the local demo uses the loopback address. Required · Fill in: 127.0.0.1Publish after changes. |
| Controlled Station Port | The platform binding stays consistent with the imported controlled station's listening port. Required · Fill in: 15040Publish after changes. |
| Common Address | Identifies the station; keep the platform binding and native messages consistent. Required · Fill in: 1Publish after changes. |
| Device Binding | deviceId 1244, clientId is this device's number; enable the binding. Required · Fill in: 1244 / FastBee_IEC104_Tutorial_01Publish after changes. |
| Information Object Address | Ten independent remote signalling addresses; 1001 is this article's writable point. Required · Fill in: 1001–1010; control 1001Publish after changes. |
| Remote Signalling Type | Single-point remote signalling maps to BOOLEAN; true is Closed, false is Open. Required · Fill in: M_SP_NA_1 / BOOLEANPublish after changes. |
| Scale and Offset | The boolean demo keeps scale 1 and offset 0, with the unit left blank. Required · Fill in: 1 / 0Publish after changes. |
| Historical Collection Group Configuration | The first configuration enabled general interrogation with a 60000-millisecond interval; this only describes the saved items and is not proof of a successful manual general interrogation in this round. Required · Fill in: interrogationEnabled on; 60000 millisecondsPublish after changes. |
| Single-Point Remote Control Template | Common address 1, information object address 1001, select-before-execute off, using direct execution. Required · Fill in: C_SC_NA_1; selectBeforeExecute offPublish after changes. |
| Publish and Application | Start the controlled station listener first, then publish and wait for the node to reach APPLIED. |
First Thing Model Configuration
| Field / Control | How to Fill |
|---|---|
| Property Permission and History | All ten items have history enabled; 1001 allows control, and the other nine items are read-only. Required · Fill in: Ten boolean properties; 1001 writablePublish after changes. |
Historical Optional General Interrogation Configuration
| Field / Control | How to Fill |
|---|---|
| Historical Optional Station-Wide General Interrogation | Only the first whitelist configuration is kept for reference; this round did not re-save or execute a manual general interrogation. Required · Fill in: Common address 1; address 0; C_IC_NA_1Publish after changes. |
FMQX Web Controlled Station
| Field / Control | How to Fill |
|---|---|
| First Imported Configuration | The IP, port, common address, and ten-point table are provided by the imported file; this round did not re-import. |
| Connection Name | The connection name visible in the current editor; read-only verification in this round. |
| Owning Group | The group visible in the current editor; read-only verification in this round. |
| Save Method | The current editor shows saving to this machine or for this use only; editing was cancelled in this round. |
| Start the Controlled Station | As a Server, listen on 15040 first, then the FMQ master station connects. Reconnect after changes. |
| Connection and STARTDT | Verify the role, station address, ten points, and 1 active connection. |
Device Remote Signalling and Raw Frames
| Field / Control | How to Fill |
|---|---|
| Set Demo Point Values | Save each of the ten-sample addresses once: odd true, even false; the recovery 1002=true and the second baseline 1001=false are saved separately by the operator. Required · Fill in: 1001–1010 once each |
| Send Telemetry | Send after saving the demo point value; wait for the platform to update before switching to the next address. |
| Raw Frame | Verify by time the direction, type, cause code, station address, point address, and the complete HEX. |
Platform Control and Feedback
| Field / Control | How to Fill |
|---|---|
| Platform Retained Current Values | The closing complete ten-point image was captured after the final stop; 1001 and 1002 are both Closed, and 1003 to 1010 remain odd Closed and even Open. |
| First Remote Signalling 1 Control | This round controls from true to false; the screenshot shows true before writing. Required · Fill in: 1001: Closed → Open断开: The first target false; sends the address 1001 single command.合上: This round's first pre-write value; verify the actual target with the native frames. |
| Native Remote Control Feedback | cause6 activation request, cause7 activation confirmation, cause10 activation termination; an independent remote signalling report follows. |
Stop and Recovery
| Field / Control | How to Fill |
|---|---|
| Normal Stop and Explicit Recovery | Unpublish after a normal disconnect; to recover, start the controlled station first, then explicitly republish. Reconnect after changes. |
| New Control After Recovery | The operator first saves and sends the 1001=false baseline, then the platform controls true. Required · Fill in: 1001: Open → Closed断开: The pre-write baseline set by the operator; must be described separately from the later remote control.合上: The second platform target; sends a new native single command. |
| Independent Report After Control | Only select address 1001 and send telemetry without saving the point value; false the first time, true the second time. |
| End and Preserve | Finally stop the controlled station and unpublish, keeping the product, device, model, session, and the queried history. Reconnect after changes. |
This Round's Historical Data
| Field / Control | How to Fill |
|---|---|
| History Filtering | Select this controlled station and Remote Signalling 1 to 10 for the ten samples; select only Remote Signalling 1 for the control-recovery window. |
| Complete Time Range | Ten samples 02:05:17 to 02:05:31; control and recovery 02:05:41 to 02:06:13, all on 2026-10-16. |
| Record-by-Record History Values | For the ten samples, read the column corresponding to each row's address; the six Remote Signalling 1 rows are distinguished by source and are not called six controls. |
| Refresh Results | Keep the device, fields, and complete time conditions, and click the refresh button at the top right of the result area. |
Where to Check First When Problems Occur
| Symptom | Possible Cause | Where to Check First | How to Recover |
|---|---|---|---|
| Controlled station not connected | The listener is not started, the endpoint does not match, or the current configuration is not applied | First verify this article's listening port 15040, then check the publish APPLIED status and STARTDT | Start the original controlled station, explicitly republish, and wait for application before sending. |
| Remote signalling values or history do not correspond | The station address, point address, mapping, or time window is inconsistent | Verify common address 1, 1001 to 1010, the boolean values, and this round's times | After fixing, send only one new point and verify the corresponding field. |
| The platform has control records but the result is unconfirmed | The native end and the independent state have not been verified yet | Associate cause6/7/10 with the subsequent independent type1/cause3 | Wait for the current command to end, only select the address and send telemetry, and do not manually save the point value. |
| The other history table columns are empty | That report only contains one address | Read the value in the column of that record's address | Continue checking the independent rows for the other addresses. |